EDH0162En1040 – 06/99
3.172
MM4005
XH — Read home preset position
Usage
IMM
PGM
MIP
Syntax
xxXH
Parameters
Description
xx
[int]
— Axis number.
Range
xx
—
1
to
4.
Units
xx
— None.
Defaults
xx
Missing: Error B.
Out of range: Error B.
Floating point: Error A.
Description
This command reads the home preset position value. This value is the one
loaded in the position counter after a home search is initiated and home is
found.
NOTE
See the Motion Control Tutorial Section for a description of the Home
search algorithm.
Returns
xxXHnn
.
xx
—
Axis number.
nn
—
Home preset position.
Errors
A
—
Unknown message code.
B
—
Incorrect axis number.
S
—
Communication time-out.
Rel. Commands
SH
—
Set home preset position.
OR
—
Search for home.
Example
2XH
|
Read home preset position for axis #2.
2XH8.2
|
Controller returns a home preset position of 8.2 units.