Newave_OPM_PV11_PV31 _GB_250805.doc Installation
Page 18
FA1 (A)
FA2 (A)
FA3 (A)
7,5kVA 32 A (10x38)
ultrafast
50 A (14x51)
GL/GC
32 A (10x38)
ultrafast
10kVA
32 A (10x38)
ultrafast
50 A (14x51)
GL/GC
32 A (10x38)
ultrafast
15kVA
32 A (10x38)
ultrafast
80 A (22x58)
GL/GC
50 A (14x51)
ultrafast
PowerValue
TM
31
Cabinet “A” rear view
Mains Input
(Single Feed)
Separate Bypass
(For Dual
Feed)
Output
(To Load)
3L1 3N PE
PE 2L1 2N
Cabinet A
Elements:
FA1 Rectifier
Line
Fuse
FA2 Bypass
Line
Fuse
FA3 Battery
Fuse
IA1 Maintenance
Bypass
IA2 Output
Switch
JD1
Smart Port-RS232 (SUB-D9P/F)
X1-X21 Dry Port-volt-free contacts on
terminal block
(see chapter 3.8.2)
1N 1L1 1L2
PE
1L3
Figure 2
Connection of UPS POWERVALUE 7.5,10 and 15 kVA with three phase input mains supply. Output
Load connection terminals (SINGLE INPUT FEED).
IA1 IA2 FA2 FA1
FA3
In/Out Terminal Block
+ N -
Only for
external
battery
X1-X21
JD1
SNMP
Note: the number of fans depend on
the power of the UPS.