Newave_OPM_PV11_PV31 _GB_250805.doc Installation
Page 7
3 Installation
3.1 INTRODUCTION
This chapter contains all the necessary information for the correct unpacking, positioning, cabling and
installation of the UPS
PowerValue
TM
.
ALL THE OPERATIONS IN THIS SECTION MUST BE PERFORMED BY AUTHORISED
ELECTRICIANS OR BY QUALIFIED PERSONNEL.
NEWAVE will take no responsibility for any personal or material damage caused by
incorrect cabling or operations or activities, which are not carried out as per the
instructions contained in this manual.
3.1.1 Receipt of the UPS
Upon receiving the UPS, carefully examine the packing container and the UPS for any sign of physical
damage. In case of rupture or suspect inform immediately:
a) The carrier and
b) NEWAVE
SA.
Ensure that the received UPS corresponds to the material indicated in the delivery note.
The packing container of the
PowerValue
TM
protects it from mechanical and environmental damage.
To increase its protection the UPS is wrapped with a plastic sheet.
3.1.2 Nameplate
The technical specifications of the
PowerValue
TM
are provided on the nameplate, which is situated at
the front of the UPS. Check if it corresponds to the purchased material mentioned in the delivery note.
3.2 UNPACKING
When unpacking the UPS observe the "FRAGILE" and "ARROW" on the packing container.
Perform the following steps to unpack the UPS:
•
Cut wrappers and remove packing container by pulling it upwards;
•
Remove the plastic cover from the UPS;
•
Remove pallet from the UPS;
•
Retain the packaging materials for future shipment of the UPS;
•
Examine the UPS for any sign of damage. Notify your carrier or supplier immediately if
damage is apparent.
3.3 BATTERIES
The standard batteries of
PowerValue
TM
are sealed, maintenance-free batteries, internally mounted
and will typically be connected when the UPS is commissioned.
The battery life depends very much on the ambient temperature. A temperature range b18°
and +23°C will achieve the optimum battery life.
If the UPS is delivered without batteries, NEWAVE is not responsible for any damage or
malfunctioning caused to the UPS by incorrect wiring
!