Newave_OPM_PV11_PV31 _GB_250805.doc Installation
Page 15
Under the connection terminal of the UPS there is a cable-fixing rail to ensure that the cables have
been fastened properly
3.6.16 Connection of the Mains Supply
After the UPS has been unpacked and brought to its final position the authorized technician may start
with the cabling.
ALL THE OPERATIONS IN THIS MANUAL MUST BE PERFORMED BY AUTHORISED
ELECTRICIANS OR BY QUALIFIED INTERNAL PERSONNEL.
To ensure protection of the personnel during the installation of the UPS make sure that the
connections are performed under the following conditions:
•
No mains voltage is present;
•
All loads are shut down and disconnected;
•
UPS PowerValue
TM
is shut down and voltage-free.
Remove the terminal cover of the UPS
Before connecting the input power cables make sure that:
•
UPS-System is placed in its correct position;
•
Maintenance Bypass IA1 is open in position OFF;
Connect the input power cable coming from the LV-Distribution Board to the terminals of the UPS in
accordance with Figures 2 and 3.
NOTE: Neutral input wire must always be connected!
NOTE: The UPS PowerValue
TM
is provided with facilities for both single feed (one common input
cable for rectifier and bypass) and dual feed (two separate input cables for rectifier and bypass
respectively).
The standard UPS PowerValue
TM
is always supplied with facilities for a single feed. If dual feed
is required please contact next Service Centre
.
3.6.17 Single Input Feed
To achieve correct Input Cabling see Drawing in see Figures 3.
For single input feed connect the mains input cable to UPS Terminal Block according to the following
table:
For minimum recommended Input Cable Sections and Fuse Ratings for the PowerValue
TM
see table in
Section Technical Specifications at the end of this User Manual.
Under the connection terminal of the UPS there is a cable-fixing rail to ensure that the cables have
been fastened properly.
3.6.18 Dual Input Feed
NOTE
: In the standard version PowerValue
TM
comes with SINGLE INPUT FEED. If DUAL
INPUT FEED is required please contact your next service office before performing any cabling.
MAINS INPUT CABLE
UPS TERMINAL
Phase L1
1L1
Phase L2
1L2
Phase L3
1L3
NEUTRAL 1N
EARTH PE
!
!