Newave_OPM_PV11_PV31 _GB_250805.doc Operation
Page 26
4.3 DESCRIPTION OF THE LCD
4.3.1 Status
Screens
DESCRIPTION
LCD-DISPLAY
1
Load is protected by UPS power (load is supplied
by inverter(Normal Operation)
LOAD
PROTECTED
2
Load is not protected by UPS power it is supplied
by mains power (load on bypass)
LOAD
NOT PROTECTED
3
Load supply completely interrupted. UPS has been
switched off by “ON/OFF” buttons
LOAD OFF
SUPPLY FAILURE
4.3.2 Main
Menu
Screen
DESCRIPTION
LCD-DISPLAY
1
Logging Control. A log of the last 64 events is
stored in the Power Management Display.
Æ
EVENT LOG
MEASUREMENTS
2
In Menu Measurements: monitor voltages,
power,frequencies, currents, autonomy etc.
Æ
MEASUREMENTS
COMMANDS
3
The Command Menu enables to perform the
commands “Load to inveter”, Load to bypass,
battery test.
Æ
COMMANDS
UPS
DATA
4
The UPS Data are the UPS personalized
information “serial number”
Æ
SET-UP DATA
SET-UP
USER
5
Various settings can be performed by the user:
Date/Time, automatic battery test, etc.
Æ
SET-UP USER
SET-UP
SERVICE
6
Various adjustments can be performed by the
service staff
Æ
SET-UP SERVICE
NO MORE MENU
4.3.3 Event Log Screen
DESCRIPTION
LCD-DISPLAY
1
Logging Control; a log of the last 64 events is
stored in the Power Management Display.
01
05-10-00
LOAD TO INV.
14-38-59
2
Every stored event is identified with a sequential
number and time stamp.
02
05-10-00
LOAD TO BYP.
14-38-56
3
All events and alarms are indicated with their date
and time of appearance.
03
05-10-00
LOAD OFF
14-37-14
4.3.4 Measurements
Screen
DESCRIPTION
LCD-DISPLAY
1
Battery Runtime
BATT. RUN TIME (MIN)
00h 00m
2
UPS-Output Frequency
OUTPUT FREQUENCY (HZ)
50.00
3
Bypass Frequency.
BYPASS FREQUENCY (HZ)
50.00
4
Battery Voltage
BATTERY VOLTAGE (V)
+ 0.0 - 0.0
5
Battery Charger Current
BATT. CHARGE CUR. (A)
+ 0.0 - 0.0
6
Discharge Current.
DISCHARGE CURRENT (A)
00.00
7
Rectifier Voltage of all three phases or single
phase
RECTIFIER VOLTAGE (V)
230 230 230