Newave_OPM_PV11_PV31 _GB_250805.doc Installation
Page 19
FA1 (A)
FA2 (A)
FA3 (A)
7,5kVA 32
A
(10x38)
ultrafast
50 A
(14x51)
GL/GC
30 A
(10x38)
ultrafast
10kVA 32
A
(10x38)
ultrafast
50 A
(14x51)
GL/GC
30 A
(10x38)
ultrafast
15kVA 32
A
(14x51)
ultrafast
80 A
(22x58)
GL/GC
50 A
(14x51)
ultrafast
20kVA 32
A
(10x38)
ultrafast
100 A
(22x58)
GL/GC
50 A
(10x38)
ultrafast
Mains Input
(Single Feed)
Remove Link between 2L1
and 1L1for Dual Feed
Separate Bypass
(For Dual
Feed)
Output
(To Load)
2L1 1L1 1L2 1L3 PE
3L1 3N PE
PE 2N 1N
Cabinet B and C
Elements:
FA1 Rectifier
Line
Fuse
FA2 Bypass
Line
Fuse
FA3 Battery
Fuse
IA1 Maintenance
Bypass
IA2 Output
Switch
JD1
Smart Port-RS232 (SUB-D9P/F)
X1-X21 Dry Port-volt-free contacts on
terminal
block (see chapter 3.8.2)
PowerValue
TM
31
Cabinet B and C, front view
Figure 3 Connection of UPS POWERVALUE 7.5, 10, 15 and 20kVA with three phase input mains supply. Output
Load connection terminals (SINGLE INPUT FEED).
In/Out Terminal Block
+ N -
Only for external
battery
SNMP
JD1
X1-
X21
FA1
IA1 IA2 FA2
FA3