Newave_OPM_PV11_PV31 _GB_250805.doc Installation
Page 22
3.8.2 DRY PORT (volt-free contacts)
Description:
The DRY PORT may be used for:
•
Connection of remote shutdown facilities (see paragraph 7.2);
•
Connection of Remote Status Panel (see paragraph 7.3);
•
Provision of signals for the automatic and orderly shutdown of servers
•
or IBM AS400, etc.
Definition of terminals on DRY PORT :
X2
X16
X17
X18
X19
X20
X21
X1
X3
X5
X6
X7
X8
X9
X10
X11
X12
X13
X14
X15
NO
COM
NC
MAINS
FAILURE
NO
COM
NC
NO
COM
NC
LOAD
TO
INVERTER
NO
COM
NC
BATTERY
LOW
NO
COM
NC
LOAD
ON
MAINS
+
-
X4
COMMON
ALARM
GEN-ON
+12V 100mA
GND
+
-
REMOTE
SHUTDOWN
NC
Figure 3.10
DRY PORT Connections
All volt free contacts are rated 60 VAC max. and 500 mA max.