Section 75
00-02-0878
2013-03-07
- 112 -
Error Messages
The following error messages can occur:
Message
Description
Engine I. value N.A.
The view is not selectable for the present engine type.
Value selected error
The value cannot be read due to the sensor error, sub-system or
module error.
“N.A.”
The value is not supported by the engine, or due to a communication
error.
Object Selection, J1939
The view lines can be configured with these available values.
NOTE:
For Modbus scaling, please see the chapter “Modbus
Communication”.
NOTE:
The engine is expected to use source address 0.
Object
PGN No.
Pri-
Ority
Start
Posi-
Tion
Of 1
st
Data
Byte
Length
(Bytes)
SPN
No.
Unit
J1939-71 Scaling
EIC speed
61444
3/6
4
2
190
RPM
0.125 rpm/bit, offset 0
EIC coolant temp.
(1)
65262
3/6
1
1
110
°C
1 deg C/bit, offset -40°C
EIC oil pressure
(2)
65263
6
4
1
100
Kpa
4 kpa/bit, offset 0
EIC faults (4)
65230
6
1
1
1218
1/bit, offset 0
EIC oil temp. (3)
65262
3/6
3
2
175
°C
0.03125°C/bit, offset -273°C
EIC fuel temp.
65262
3/6
2
1
174
°C
1°C/bit, offset -40°C
EIC intake
manifold #1 P.
(also called EIC
bootst P.)
65270
6
2
1
102
kpa
2 kpa/bit, offset 0
EIC air inlet temp.
65269
6
6
1
172
°C
1°C/bit, offset -40°C
EIC coolant level
65263
6
8
1
111
%
0.4%/bit, offset 0
EIC fuel rate
65266
6
1
2
183
l/h
0.05 l/h per bit, offset 0
EIC intake
manifold 1 temp.
(also called EIC
charge air temp.)
65270
6
3
1
105
°C
1°C/bit, offset -40°C
EIC d.d. % torque
61444
3/6
2
1
512
%
1%/bit, offset -125%
EIC actual %
torque
61444
3/6
3
1
513
%
1%/bit, offset -125%
EIC acc. pedal
pos.
61443
3/6
2
1
91
%
0.4%/bit, offset 0
Содержание EMS-GC10
Страница 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Страница 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Страница 32: ...Section 75 00 02 0878 2013 03 07 26 Mode Shift NOTE To enable mode shift a digital input has to be set up ...
Страница 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Страница 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Страница 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Страница 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Страница 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Страница 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Страница 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Страница 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Страница 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Страница 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Страница 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Страница 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...
Страница 75: ...Section 75 00 02 0878 2013 03 07 69 Stop ...
Страница 183: ...Section 75 00 02 0878 2013 03 07 177 ...