Digital Inputs
The unit has a number of binary inputs, some are configurable and some are not.
Input Function
Auto Semi Test Man Block
Configurable
Input Type
1
Shutdown override
X
X
X
X
X
Configurable
Constant
2
Access lock
X
X
X
X
X
Configurable
Constant
3
Binary running detection
X
X
X
X
X
Configurable
Constant
4
Remote start
X
X
Configurable
Pulse
5
Remote stop
X
X
Configurable
Pulse
6
Test
X
X
X
X
Configurable
Pulse
7
Auto
X
X
X
X
Configurable
Pulse
8
Manual
X
X
X
Configurable
Pulse
9
Block
X
X
X
X
Configurable
Constant
10 Remote GB ON
X
X
Configurable
Pulse
11 Remote GB OFF
X
X
Configurable
Pulse
12 Remote MB ON
X
X
Configurable
Pulse
13 Remote MB OFF
X
X
Configurable
Pulse
14 Remote alarm acknowledge
X
X
X
X
X
Configurable
Constant
15 Auto start/stop
X
Configurable
Constant
16 Remove starter
X
X
X
X
Configurable
Constant
17 GB position ON
X
X
X
X
X
Configurable
Constant
18 GB position OFF
X
X
X
X
X
Configurable
Constant
19 MB position ON
X
X
X
X
X
Configurable
Constant
20 MB position OFF
X
X
X
X
X
Configurable
Constant
21 Emergency stop
X
X
X
X
X
Not configurable
Constant
22 Low speed
X
X
X
Configurable
Constant
23 Temperature control
X
X
X
Configurable
Constant
24 Battery test
X
X
Configurable
Pulse
25 Mains Okay
X
X
X
X
X
Configurable
Pulse
26 GB close inhibit
X
X
X
X
Configurable
Constant
27 MB close inhibit
X
X
X
X
X
Configurable
Constant
28 Enable mode shift
X
X
X
X
X
Configurable
Constant
29 Start enable
X
X
X
X
Configurable
Constant
30 Alternative start
X
X
X
X
X
Configurable
Constant
31 Switchboard error
X
X
X
X
X
Configurable
Constant
32 Total test
X
X
X
X
X
Configurable
Constant
33 GB spring loaded
X
X
X
X
X
Configurable
Constant
34 MB spring loaded
X
X
X
X
X
Configurable
Constant
35 D+ (digital running feedback)
X
X
X
X
X
Configurable
Constant
36 Inhibit Engine alarms
X
X
X
X
X
Configurable
Constant
Содержание EMS-GC10
Страница 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Страница 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Страница 32: ...Section 75 00 02 0878 2013 03 07 26 Mode Shift NOTE To enable mode shift a digital input has to be set up ...
Страница 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Страница 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Страница 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Страница 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Страница 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Страница 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Страница 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Страница 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Страница 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Страница 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Страница 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Страница 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...
Страница 75: ...Section 75 00 02 0878 2013 03 07 69 Stop ...
Страница 183: ...Section 75 00 02 0878 2013 03 07 177 ...