Section 75
00-02-0878
2013-03-07
- 120 -
Engine Type
MTU
MDEC
MTU
ADEC
MTU
J1939Smart
Connect
Scania
EMS
Scania
EMS S6
Volvo Penta
Volvo
Penta
EMS2
Command
Preheat
-
-
-
-
-
-
X
Start/Stop
-
X
X
-
X
-
X
Engine Speed
-
X
X
-
X
-
X
Nominal Frequency
-
X
X
-
X
-
X
Governor gain
-
-
-
-
-
-
-
Idle speed
-
X
X
-
X
-
X
Droop
-
X
X
-
X
-
X
Shutdown override
-
-
X
-
X
-
X
Engine overspeed test
-
-
X
-
-
-
-
Enable cylinder cut out
-
X
X
-
-
-
-
Intermittent oil priming
-
-
X
-
-
-
-
Engine operating mode
-
-
X
-
-
-
-
Demand switch
-
X
X
-
-
-
-
Trip counter reset
-
X
X
-
-
-
-
Engine speed GOV parameter command
-
-
X
-
-
-
-
NOTE:
For engine types not mentioned, CANbus control is not supported.
In these cases, start/stop etc. must be sent to the controller using
hardwired connections.
NOTE:
The parameter number 7563 has to be used for enabling or
disabling the transmission of all the EMS-GC10 unit EIC control frames
listed in the above table.
EIC 50 Hz – 60 Hz Switch
If the set point f nominal is changed in the EMS-GC10 between 50 and 60 Hz then the change
is made with a frequency ramp of 2 Hz per second. This frequency ramp is used when
switching between nominal settings 1-4 or if the parameter of the nominal frequency is
changed between 50 and 60 Hz.
EIC Droop
There are two ways of obtaining a speed droop:
For engines where the droop command or set point can be sent to the engine controller the
droop setting in parameter 2771 is the actual droop that is being used and this set point is sent
to the ECU. This method is referred to as “EIC droop”.
For engines where the droop command or set point cannot be sent to the engine controller, the
droop setting in parameter 2771 is used for droop emulation in the EMS-GC10. This method is
referred to as “EIC droop emulation”.
Содержание EMS-GC10
Страница 1: ...00 02 0878 Section 75 2013 03 07 GensetControllerUnit ModelEMS GC10 Operator sManual ...
Страница 14: ...Section 75 00 02 0878 2013 03 07 8 Menu Structure Diagram ...
Страница 32: ...Section 75 00 02 0878 2013 03 07 26 Mode Shift NOTE To enable mode shift a digital input has to be set up ...
Страница 33: ...Section 75 00 02 0878 2013 03 07 27 MB Open Sequence ...
Страница 34: ...Section 75 00 02 0878 2013 03 07 28 GB Open Sequence ...
Страница 35: ...Section 75 00 02 0878 2013 03 07 29 Stop Sequence ...
Страница 36: ...Section 75 00 02 0878 2013 03 07 30 Start Sequence ...
Страница 37: ...Section 75 00 02 0878 2013 03 07 31 MB Close Sequence ...
Страница 38: ...Section 75 00 02 0878 2013 03 07 32 GB Close Sequence ...
Страница 39: ...Section 75 00 02 0878 2013 03 07 33 Load Takeover LTO ...
Страница 40: ...Section 75 00 02 0878 2013 03 07 34 Island Operation ...
Страница 41: ...Section 75 00 02 0878 2013 03 07 35 Automatic Mains Failure AMF ...
Страница 42: ...Section 75 00 02 0878 2013 03 07 36 Test Sequence ...
Страница 48: ...Section 75 00 02 0878 2013 03 07 42 Stop Sequence The drawings illustrate the stop sequence ...
Страница 74: ...Section 75 00 02 0878 2013 03 07 68 Start ...
Страница 75: ...Section 75 00 02 0878 2013 03 07 69 Stop ...
Страница 183: ...Section 75 00 02 0878 2013 03 07 177 ...