Level Plus

®

 SoClean

®

Operation Manual

3. Introduction

3.1 Purpose and use of this manual

The content of this technical documentation and of its various 
annexes is intended to provide information on mounting, installation 
and commissioning by qualified service personnel according to IEC 
60079-14 and local regulations or MTS trained service technicians.

3.2 Used symbols and warnings

Warnings are intended for your personal safety and for avoidance 
of damage to the described product or connected devices. In this 
documentation, safety information and warnings to avoid dangers that 
might affect the life and health of personnel or cause material damage 
are highlighted by the preceding pictogram, which is defined below.

4. Safety instructions

4.1 Intended use

The liquid level transmitter is intended to be used to measure the level 
of liquid(s) contained by a structure as well as the temperature of the 
liquid.  The product may only be used for the applications defined 
under item 1 to item 4 below and only in conjunction with third-party 
devices and components recommended or approved by MTS Sensors.  
As a prerequisite of proper and safe operation, the product requires 
correct transport, storage, mounting and commissioning and must be 
operated with utmost care.

1. Application does not exceed product’s performance specification in 

section 5.6.

2. Product may only be installed in hazardous areas as specified by 

approval certifications in section 12 following special conditions of 
safe use outlined in section 12 or in safe areas.

3. The liquid(s) being measured are compatible with the selected 

wetted parts of the product.

4. MTS floats should be used for proper functionality and safety 

approval.

4.2 Foreseeable misuse

Important:

Before starting the operation of the equipment read this documentation 
thoroughly and follow the safety information.

Symbol

Meaning

NOTICE

This symbol is used to point to situations
that may lead to material damage, and/or personal 
injury.

4.3 Installation, commissioning and operation

1. Wear proper personal protection equipment such as hard hat, 

safety shoes, flame resistant clothing, safety glasses, gloves, and 
hearing protection.

2. Follow the specifications given in the technical documentation.
3. Two (2) individuals are recommended to conduct proper installati-

on, commissioning, and repair of the level transmitter.

4. Ensure the equipment used in a hazardous environment is selected 

and installed in compliance with regulations governing the geogra-
phical installation and facility. Only install equipment that complies 
with the types of protection relevant to the applicable classes, 
division, zones, category, gas group, and temperature code.

5. Protect the sensor against mechanical damage during installation 

and operation.

6. Do not use damaged products and secure them against unintentio-

nal use.  Mark damaged products as being defective.

7. Connect the sensor very carefully and pay attention to the polarity 

of connections.  MTS recommends to not make connections while 
power is live.  

8. Before turning on power, ensure that nobody’s safety is jeopar-

dized by starting level transmitter and/or process.

9. Regularly follow preventative maintenance to prevent safety risks.

10. Make sure that no wire strands are loose or sticking out of the   

  terminal block connection which could short and cause a problem.

11. Make sure that no wire strands, including shield, are in contact  

  with the electronic module enclosure.

5. Product overview

The Level Plus

®

 SoClean

®

 Liquid-Level transmitter is a continuous 

multi-functional magnetostrictive transmitter that provides product 
level, interface level, and temperature to the user via Modbus, DDA, 
Analog (4-20 mA), or HART

®

. Magnetostrictive technology is one of 

the most accurate and repeatable level technologies available to date.  

Forseeable misuse

Consequence

Process Temperature out of range

Signal Degradation, Possible Damage 
to Sensor
See Section 5.6 for Specifications

Power Supply out of range

No Communication, Possible Dam-
age to Sensor
See Section 5.6 for Specifications

Process Pressure out of range

Possible Damage to Sensor,
See Section 5.6 for Specifications

Improper Chemical Compatibility

Possible Damage to Sensor,
Customer Must Select Wetted Mate-
rial that is compatible with liquid(s) 
in tank

Modifying Sensor

Warranty Void, Hazardous Approval 
Void Customer should contact facto-
ry for custom unit

Improper Grounding

Possible Damage to Sensor, Full 
Protection Compromised,
See Section 7.6 for Grounding

Forseeable misuse

Consequence

Wrong sensor connection

Possible damage to electronics
See Section 7 for Electrical 
Connections

Improper Installation

Physical damage to packaging
See Section 6 for Installation

Installation in unapproved 
Hazardous Area

Potential Spark
See Section 12 for Agency 
Information

Table 1: Foreseeable misuse

Содержание Level Plus SoCLEAN

Страница 1: ...SoCLEAN Level Plus Operation Manual Magnetostrictive Liquid Level Transmitters with Temposonics Technology...

Страница 2: ...6 1 Safety grounding 14 7 6 2 Shield grounding 14 7 7 Safety barriers 15 8 Commissioning 16 8 1 Training 16 8 2 Tools 16 8 3 Setup software 16 8 4 Commissioning steps 16 8 4 1 Modbus or DDA 16 8 4 2 H...

Страница 3: ...800 633 7609 e mail levelplus mts com Germany General Tel 49 2351 9587 0 Fax 49 2351 56491 e mail info de mtssensors com http www mtssensors com Mailing and shipping address MTS Sensor Technologie Gm...

Страница 4: ...al two way communications system that serves as the base level network in a plant or factory automation environment Developed and administered by the fieldbus FOUNDATION G GOVI Gross Observed Volume o...

Страница 5: ...density measurement is given the allow able values are 32 F to 150 F S Specific Gravity The density ratio of a liquid to the density of water at the same condi tions Sphere Radius The internal radius...

Страница 6: ...sioning and repair of the level transmitter 4 Ensure the equipment used in a hazardous environment is selected and installed in compliance with regulations governing the geogra phical installation and...

Страница 7: ...THE RECIPIENT m MTS SYSTEMS CORPORATION SENSORS DIVISION 3001 SHELDON DRIVE CARY NC 27513 METRIC FIRST ANGLE C LL drawing 1 1 DRAWN BY 114 mm 4 5 in 127 mm 5 in 124 mm 4 9 in 132 mm 5 2 in 87 mm 3 4 i...

Страница 8: ...el 3 A sanitary hastelloy Teflon and Nitrophyl for both product level and interface level To be able to accurately detect the interface level there needs to be a difference of at least 0 05 in specifi...

Страница 9: ...w terminal C NEMA housing w connector D Single cavity with display E Dual cavity with display L SS single cavity w display g Process connection type 1 NPT adjustable 2 BSPP adjustable 4 Sanitary Tri C...

Страница 10: ...accessories are shown in the Accessories Catalog 551103 L P S a b c d e f g h i Gas group A Group A B Group B C Group C D Group D 1 IIA 2 IIB 3 IIC X None p Special S Standard Product m o Length no d...

Страница 11: ...MA Type 4X IP65 Humidity 0 to 100 relative humidity non condensing Operating temperatures Electronics 40 C 40 F to 71 C 160 F Sensing element 40 C 40 F to 125 C 257 F Temperature element 40 C 40 F to...

Страница 12: ...rs factory direct services for these same functions Contact MTS to discuss training or factory direct services before starting 6 2 Stilling wells and guide poles Level Plus transmitters can be mounted...

Страница 13: ...consists of having only one device on the loop as shown in Figure 8 This topology is not usually used with a bus network since it does not take advantage of placing multiple devices on a loop PLC Lev...

Страница 14: ...rectly to the earth ground lug inside the housing Run an earth ground directly to the ground lug on the outside of the housing 7 6 2 Shield grounding Warning The shield ground does not meet the requir...

Страница 15: ...0 0 F Li 0 0 mH Pi 21 5 mW Analog 1 per Loop Ui 28 Vdc Ii 120 mA Ci 0 F Li 5 H Pi 840 mW Table 3 Safety barrier entity parameter references Table 4 Safety barrier entity parameter references Supplier...

Страница 16: ...to make sure that the level transmitter and surrounding environ ment are in operating condition Hazardous Area Label is present and legible Hazardous Area approval is correct for installation There a...

Страница 17: ...correctly Technical support can assist you with troubleshooting part replacement and Returned Material Authorization RMA information if required 9 4 2 Severe Service Applications 9 4 2 1 Perform Inspe...

Страница 18: ...ce Manual MTS Part 551702 12 Agency information 12 1 Approvals overview The Notified Body is designated in the 13th digit of the model number and the Protection Method is designated in the 14th digit...

Страница 19: ...OMPONENTS MAY IMPAIR INTRINSIC SAFETY REFER TO INSTALLATION DRAWING FOR CAUTION WARNINGS INSTALL PER DRAWING 651543 1 SUPPLY VOLTAGE 28 VDC Level Plus Transmitter 3 L1 L2 17 53 69 7 5 POINT SIZE MTS T...

Страница 20: ...CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC 6 ASSOCIATED APPARATUS MANUFACTURER S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS...

Страница 21: ...ITIMATELY IN THE PRIOR POSSESSION OF THE RECIPIENT m MTS SYSTEMS CORPORATION SENSORS DIVISION 3001 SHELDON DRIVE CARY NC 27513 METRIC FIRST ANGLE D 651543 1 2 2 DRAWN BY MS NO REVISIONS SHALL BE MADE...

Страница 22: ...APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC 6 ASSOCIATED APPARATUS MANUFACTURER S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT 7 ONLY USE NEC e g FM APPROVED...

Страница 23: ...ESSION OF THE RECIPIENT m MTS SYSTEMS CORPORATION SENSORS DIVISION 3001 SHELDON DRIVE CARY NC 27513 METRIC FIRST ANGLE D 651544 1 LEVEL 2 2 DRAWN BY MS 1 1 NO REVISIONS SHALL BE MADE WITHOUT NOTIFICAT...

Страница 24: ...sion 3001 Sheldon Drive Cary N C 27513 INTRINSICALLY SAFE CL I Div 1 GR ABCD Ex ia IIC T4 Ga Gb Ta 50 C TO 71 C IP65 REFER TO INSTALLATION DWG 651543 2 FOR CAUTION WARNINGS WARNING SUBSTITUTION OF COM...

Страница 25: ...H GROUND DIRECTLY OR THROUGH THE EQUIPMENT ON WHICH IT IS MOUNTED 5 CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC 6 ASSOCIATED APPARATUS MANUFA...

Страница 26: ...L BE MADE WITHOUT THE NOTIFICATION TO APPROVAL AGENCY S B 7847 UPDATED IP RATING FOR HOUSING TYPES MS 12 2 14 E C 7898 UPDATED TEMPERATURE ON NOTE 12 TO 71 C MS 2 23 15 D 8037 ADDED FRENCH TRANSLATION...

Страница 27: ...NNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC 6 ASSOCIATED APPARATUS MANUFACTURER S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT 7 ONLY USE...

Страница 28: ...IVISION 3001 SHELDON DRIVE CARY NC 27513 METRIC FIRST ANGLE D 651544 2 LEVEL 2 3 DRAWN BY MS 1 1 NO REVISIONS SHALL BE MADE WITHOUT NOTIFICATION TO APPROVAL AGENCY S B 7847 UPDATED IP RATING FOR HOUSI...

Страница 29: ...IAL NO DATE CODE ENTITY PARAMETERS SEE PRINT REFERENCE CHART 7570 RELEASE TO PRODUCTION 1725 Level Plus Transmitter P N 551629 3 Rev B R3 30 1 78 07 1 78 07 28 7 15 34 6 69 85 2 75 IP RATING WAS 66 78...

Страница 30: ...CTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC 6 ASSOCIATED APPARATUS MANUFACTURER S INSTALLATION DRAWING MUST BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT 7 ONLY USE AT...

Страница 31: ...EGITIMATELY IN THE PRIOR POSSESSION OF THE RECIPIENT m MTS SYSTEMS CORPORATION SENSORS DIVISION 3001 SHELDON DRIVE CARY NC 27513 METRIC FIRST ANGLE D 651543 3 2 2 DRAWN BY MS NO REVISIONS SHALL BE MAD...

Страница 32: ...HICH IT IS MOUNTED 5 CONTROL EQUIPMENT CONNECTED TO ASSOCIATED APPARATUS MUST NOT USE OR GENERATE MORE THAN 250 VRMS OR VDC 6 ASSOCIATED APPARATUS MANUFACTURER S INSTALLATION DRAWING MUST BE FOLLOWED...

Страница 33: ...SSESSION OF THE RECIPIENT m MTS SYSTEMS CORPORATION SENSORS DIVISION 3001 SHELDON DRIVE CARY NC 27513 METRIC FIRST ANGLE D 651544 3 LEVEL 2 2 DRAWN BY MS 1 1 NO REVISIONS SHALL BE MADE WITHOUT NOTIFIC...

Страница 34: ...atmospheres Ger te und Schutzsysteme zur Verwendung in explosionsgef hrdeten Bereichen Appareils et syst mes de protection tre utilis s en atmosph res explosibles 2004 108 EC Electromagnetic Compatibi...

Страница 35: ...8 North Qinzhou Road 200233 Shanghai China Tel 86 21 6485 5800 Fax 86 21 6495 6329 info cn mtssensors com www mtssensors com ITALY MTS Systems Srl Sensor Division Via Camillo Golgi 5 7 25064 Gussago B...

Отзывы: