Level Plus
®
SoClean
®
Operation Manual
8. Commissioning
8.1 Training
Commissioning should only be conducted by qualified service personnel
according to IEC 60079-14 and MTS trained service technicians and local
regulations. MTS offers web based and in person training for installation,
commissioning, maintenance, and repair. MTS also offers factory direct
services for these same functions. Contact MTS to discuss training or
factory direct services before starting.
8.2 Tools
»
Channel Lock pliers
»
RS485 to USB Converter (MTS Part # 380114)[Modbus and DDA]
»
PC
»
Linear Regulated Power Supply
»
MTS Setup Software
»
HART
®
to USB Converter (MTS Part # 380068)[HART
®
]
8.3 Setup software
MTS offers Setup Software that is shipped with the level transmitter and
is also available for download from www.mtssensors.com. The Setup
Software is to be used for installation, commissioning, and troubleshoo-
ting. For further details on how to use the setup software consult the
Modbus Interface Manual (MTS Part# 551700), the DDA Interface Manual
(MTS Part# 551701), and HART
®
Interface Manual MTS Part# 551702).
8.4 Commissioning steps
8.4.1 Modbus or DDA
1. Consult Section 4.3 before starting
2. Remove level transmitter from shipping container.
3. Insert pipe into float(s) making sure float(s) are in the active
range. Install product float first.
4. Connect power, RS485 to USB converter, and PC.
5. Open MTS Setup Software.
6. Establish Communication.
7. For DDA Interface – Set Address.
8. For Modbus Interface – Set Address, Enter Strap Table, Setup Volume
Correction Method.
9. Disconnect Power and Communication. Remove floats. Prepare
level transmitter for transport to the top of the tank.
10. Complete Installation in Section 6.4.
11. Have qualified technician perform hand measurement. Enter hand
measurement into MTS Setup Software and calibrate.
12. Store all settings as backup file according to site name and tank
number.
Note:
For Additional details consult the protocol specific Modbus Interface
Manual (MTS Part #551700), DDA Interface Manual (MTS Part
#551701), and HART
®
Interface Manual (MTS Part #551702).
9.3 Inspection
Below are some standard items that should be inspected on a regular
basis to make sure that the level transmitter and surrounding environ-
ment are in operating condition.
»
Hazardous Area Label is present and legible
»
Hazardous Area approval is correct for installation
»
There are no visible unauthorized modifications
»
Electrical connections are tight
»
Condition of enclosure gasket is satisfactory
»
No water ingress (white powder)
»
No obvious damage to cable
»
Sealing of conduit or cable gland is satisfactory
»
Earth ground is satisfactory
»
Single or Dual Cavity Enclosure threads are not damaged
»
Housing o-ring is not damaged or cracked
»
No corrosion on visible parts
»
Printed circuit boards are clean and undamaged
9.4 Preventative maintenance
Level Plus
®
level transmitters do not typically require preventative
maintenance but may require preventative maintenance dependent
on the application. For general purpose applications where there is
no potential for buildup on the pipe and/or float there is no need for
preventative maintenance but routine inspection is still suggested.
For severe service applications where there is potential for buildup on
the pipe and/or float then preventative maintenance is required.
9. Maintenance
9.1 Training
Maintenance should only be conducted by qualified service personnel
according to IEC 60079-14 and MTS trained service technicians and
local regulations. MTS offers web based and in person training for
installation, commissioning, maintenance, and repair. MTS also offers
factory direct services for these same functions. Contact MTS to discuss
training or factory direct services before starting.
9.2 Tools
»
Channel Lock pliers
»
RS485 to USB Converter (MTS Part # 380114)
»
PC
»
Linear Regulated Power Supply
»
MTS Setup Software
8.4.2 HART
®
1. Consult Section 4.3 before starting
2. Remove level transmitter from shipping container.
3. Remove bottom fixing nut, washer, spacer, and stop collar.
4. Insert flexible hose into float(s) making sure float(s) are in the active
range.
5. Connect power, HART
®
to USB converter, and PC
6. Open MTS Setup Software.
7. Establish Communication.
8. Set/Update 4 and 20 mA setpoints
9. Disconnect Power and Communication. Remove floats. Prepare
flexible level transmitter for transport to the top of the tank.
10. Complete Installation in Section 6.4.
11. Have qualified technician perform hand measurement. Enter hand
measurement into MTS Setup Software and calibrate.