6 Functions and settings
Maschinenfabrik Reinhausen 2014
90
2374092/04 EN
TAPCON® 260
Circuit E
TAPCON® 260
Figure 55: Phase difference 30 3PH
▪
The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪
The current transformer CT is looped into the outer conductor L2.
▪
The current I
L2
is ahead of voltage U
L2
-U
L1
by 30°.
▪
The voltage drop on an outer conductor is determined by the current I
L2
.
Circuit F
TAPCON® 260
Figure 56: Phase difference -30 3PH
▪
The voltage transformer VT is connected to the outer conductors L1 and
L2.
▪
The current transformer CT is looped into the outer conductor L1.
▪
The current I
L1
lags behind U
L1
-U
L2
by 30°. This corresponds to a phase
shift of -30°.
▪
The voltage drop on an outer conductor is determined by the current I
L1
.
To set the phase difference for the transformer circuit, proceed as follows: