To set the average value interval, proceed as follows:
1.
>
Configuration >
Continue >
Continue >
Memo-
ry > Press
until the desired parameter is displayed.
ð
Average value interval.
2.
Press
to increase the time or
to reduce it.
3.
Press
.
ð
The average value interval is set.
Setting event memory size
You can use this parameter to configure the event memory size. The event
memory stores instances of values exceeding or falling below the preset
threshold values (V> and V<). It stores this information in high resolution.
The maximum number of events depends on the size of the event memory:
Event memory size
256 kB
512 kB
1024 kB
2048 kB
Maximum number of
events
20
40
80
160
Table 28: Event memory size
Event lasting less than 5 minutes
If the event lasts less than 5 minutes, it is recorded in high resolution
. The
high-resolution data are first recorded 10 seconds
before the event
. If
the voltage has returned to the bandwidth
, the event is still recorded until
the overrun time of 10 seconds
has passed.
At a low resolution
, the entire process is saved.