![MR TAPCON 260 Скачать руководство пользователя страница 31](http://html.mh-extra.com/html/mr/tapcon-260/tapcon-260_operating-instructions-manual_1844363031.webp)
4 Mounting
Maschinenfabrik Reinhausen 2014
31
2374092/04 EN
TAPCON® 260
2.
Place device in 19" frame and screw down.
Figure 23: Example of device mounting in a 19" frame
Connecting device
The following section describes how to establish the electrical connection to
the device.
WARNING
Electric shock
Risk of fatal injury due to connection mistakes
► Ground the device with a protective conductor using the grounding
screw on the housing.
► Note the phase difference of the secondary terminals for the current
transformer and voltage transformer.
► Connect the output relays correctly to the motor-drive unit.
Supply the voltage via separators and ensure that current paths can be
short circuited. Fit the separator, clearly labeled, near the device's power
supply so that it is freely accessible. This will allow the device to be re-
placed with ease in the event of a defect.
Cable recommendation
Please note the following recommendation from Maschinenfabrik Reinhau-
sen when wiring the device.
Excessive line capacitance can prevent the relay contacts from breaking the
contact current. In control circuits operated with alternating current, take into
account the effect of the line capacitance of long control lines on the func-
tion of the relay contacts.
4.3
4.3.1