6 Functions and settings
Maschinenfabrik Reinhausen 2014
73
2374092/04 EN
TAPCON® 260
If the measured voltage U
actual
exceeds the set limit value
, the red LED
U>
and associated signaling relay activate. The
Overvoltage U>
message ap-
pears in the display. At the same time, the high-speed return function is acti-
vated without delay time T1. Once the set switching pulse time
has
passed, the tap position is lowered
by activating the motor-drive unit until
the measured voltage U
actual
again falls below the limit value
. The
Over-
voltage U>
message is reset.
Figure 46: Response to limit value being exceeded
1
Set limit value for overvoltage
U>
6
U
actual
: Measured voltage
2
+ B %: Upper limit
A
Value exceeds limit value
3
U
desired
: Desired value
B
Value falls below limit value
4
- B %: Lower limit
C
High-speed return is started
(lower tap-change)
5
Set switching pulse time
The following sections describe how you can set the parameters for the
overvoltage monitoring V> limit value.
Set overvoltage V< as %
The limit value is entered as a relative value (%) of the set desired value. To
set the limit value, proceed as follows:
Response to high-speed
return