![MR TAPCON 260 Скачать руководство пользователя страница 146](http://html.mh-extra.com/html/mr/tapcon-260/tapcon-260_operating-instructions-manual_1844363146.webp)
10 Messages
Maschinenfabrik Reinhausen 2014
146
2374092/04 EN
TAPCON® 260
Event message
Cause
Parallel operation error
Event message appears with the following
causes:
▪
Tap synchronization method
–
Tap position not the same
–
No master or more than one master
set
–
Invalid tap position
–
Incorrect parallel operation method se-
lected for a device
▪
Circulating reactive current minimization
method
–
Circulating reactive current limit ex-
ceeded
–
Incorrect parallel operation method se-
lected for a device
–
Only one device in active parallel oper-
ation group
Motor protection device
Event message appears if motor protective
switch triggers.
Blocking
Event message appears if the "Blocking" func-
tion is selected for the customer input and there
is a signal at the customer input
No OLTC position
Event message appears if no OLTC position is
detected.
Tap-change detection
error
Event message appears if an on-load tap-
change operation has not been detected cor-
rectly.
Table 52: Event messages