12 Overview of parameters
Maschinenfabrik Reinhausen 2014
148
2374092/04 EN
TAPCON® 260
Overview of parameters
This section contains an overview of the relevant menus and parameters.
Parameter
Setting range
Factory setting
Current setting
Parameter > Normset
Normset activation
On/Off
Off
Primary voltage
0...9,999 kV
0 kV
Secondary voltage
57...125 V
100 V
Desired value 1
49...140 V
100 V
Parameter > Control parameter
Bandwidth
0.5...9 %
1.00 %
Desired value 1
49...140 V
100.0 V
Desired value 2
49...140 V
100.0 V
Desired value 3
49...140 V
100.0 V
Desired value at 0 active
power
49...140 V
100.0 V
T1 control response
T1 linear/T1 integral
T1 linear
T1 delay time
0...600 s
40 s
T2 activation
T2 on/T2 off
T2 off
T2 delay time
1...60 s
10.0 s
Parameter > Limit values
Fct. Monitoring
On/Off
Off
Absolute limit values
On/Off
Off
I> Overcurrent
50...210 %
110 %
Tap max.
-128...128
128
Tap min.
-128...128
-128
U< blocking
On/Off
On
U< Undervoltage (%)
60...100 %
90 %
U< Undervoltage (V)
34...160 V
90.0 V
U< Delay
0...20 s
10.0 s
U< also under 30 V
On/Off
Off
U> Overvoltage (%)
100...140 %
110.0 %
U> Overvoltage (V)
34...160 V
110.0 V
Parameter > Compensation
Ur line drop comp.
-25...25 V
0.0 V
Ux line drop comp.
-25...25 V
0.0 V
Z comp. limit value
0...15 %
0.0 %
Z compensation
0...15 %
0.0 %
Parameter > Cross-monitoring
Error message
0...10 s
10 s
U prim. regulator 2
0...9,999 kV
0 kV
U sec. regulator 2
57...125 V
100.0 V