12 Overview of parameters
Maschinenfabrik Reinhausen 2014
151
2374092/04 EN
TAPCON® 260
Parameter
Setting range
Factory setting
Current setting
Output 4 measured value
Off
Output 4 upper value
-9,999...9,999
0
Output 4 lower value
-9,999...9,999
0
Output 4 upper
1 mA; 10 mA; 20 mA;
10 V
20 mA
Output 4 lower
+4 mA
Configuration > Memory
Event memory
256 k; 512 k; 1024 k,
2048 k
256 k
Average value interval
1 s
U< threshold
60...100 %
90 %
U< memory
34...160 V
90.0 V
U> threshold
100...140 %
110 %
U> memory
34...160 V
110.0 V
Table 53: Overview of parameters