![MR TAPCON 260 Скачать руководство пользователя страница 140](http://html.mh-extra.com/html/mr/tapcon-260/tapcon-260_operating-instructions-manual_1844363140.webp)
9 Fault elimination
Maschinenfabrik Reinhausen 2014
140
2374092/04 EN
TAPCON® 260
Characteristics/detail
Cause
Remedy
Device blocking
▪
Tap difference
LED illu-
minated
Tap positions of motor-drive
units ED1, ED2 and ED3 not
the same
Activate operating mode
and perform
a manual tap-change operation using
keys
or
until the tap position of
motor-drive units ED1, ED2 and ED3
have been compared.
Bandwidth set too high
-
Determine recommended bandwidth
[
66] and set parameters.
Table 45: No regulation in AUTO mode
Man-machine interface
Characteristics/detail
Cause
Remedy
Keys
▪
MANUAL/AUTO operat-
ing mode cannot be
changed
REMOTE operating mode
active and LED in key
il-
luminated.
Press
to activate LOCAL mode.
Keys
▪
LEDs in keys
and
not illuminated.
Parameter error
Reset parameters to factory settings
[
Display
▪
No display.
Contrast incorrectly set.
Voltage supply interrupted.
Check voltage supply.
Fuse faulty.
Contact Maschinenfabrik Reinhausen.
LEDs
▪
Freely configurable LED
lights up
Customized LED parameteri-
zation.
Check parameters.
LEDs
▪
LED flashing
Input signal not constant.
Check input signal.
COM1
▪
Cannot be connected to
PC using TAPCON®-
trol.
Different baud rates set.
Check baud rate set on device and PC.
Table 46: Man-machine interface
Incorrect measured values
Characteristics/detail
Cause
Remedy
Measured voltage
▪
No measured value.
Connection has no contact in
the plug terminal.
Check wiring and plug terminal.
Insulation trapped
Wire not inserted far enough.
Circuit breaker tripped.
Check fuse.
9.3