TAPCON® 260
Circuit A: 1-phase measurement in 1-phase grid
TAPCON® 260
Figure 51: Phase difference 0 1PH
▪
The voltage transformer VT is connected to the outer conductor and
neutral conductor.
▪
The current transformer CT is looped into the outer conductor.
▪
The voltage U
L1
and current I
L1
are in phase.
▪
The voltage drop on an outer conductor is determined by the current I
L1
.
Circuit B: 1-phase measurement in 3-phase grid
TAPCON® 260
Figure 52: Phase difference 0 3PHN
▪
The voltage transformer VT is connected to the outer conductors L1 and
neutral.
▪
The current transformer CT is looped into the outer conductor L1.
▪
The voltage U and current I are in phase.
▪
The voltage drop on an outer conductor is determined by the current I
L1
.