6 Functions and settings
Maschinenfabrik Reinhausen 2014
62
2374092/04 EN
TAPCON® 260
Line drop compensation cannot be performed in NORMset mode.
Set the following parameters to operate the device in NORMset mode.
Activating/deactivating NORMset
You can use this parameter to activate NORMset mode.
A manual tap-change operation is required to activate NORMset. This is
how the voltage regulator determines the bandwidth required.
If the transformer is switched off, another manual tap-change operation is
required.
To activate/deactivate NORMset mode, proceed as follows:
1.
>
NORMset
ð
NORMset activation.
2.
Press
or
to activate NORMset by selecting
On
or to deactivate
NORMset by selecting
Off
.
3.
Press
.
ð
NORMset is activated/deactivated.
Setting the primary voltage
With this parameter, you can set the voltage transformer's primary voltage.
To set the primary voltage, proceed as follows:
1.
>
NORMset > Press
until the desired parameter is dis-
played.
ð
Primary voltage.
2.
Press
to increase the value or
to reduce it.
3.
Press
.
ð
The primary voltage is set.
Setting the secondary voltage
With this parameter, you can set the voltage transformer's secondary volt-
age.
To set the secondary voltage, proceed as follows: