7 Commissioning
Maschinenfabrik Reinhausen GmbH 2021
71
6796573/02 EN
MSENSE
®
VAM
3. Press the
Accept
button to save the modified parameter.
ð
The "Restart device" dialog appears.
4. Restart the device to apply the changed language setting.
7.4 Setting date and time
You can set the date and time in the following ways:
▪ Manually
▪ Time synchronization via control system (SCADA)
▪ Time synchronization via SNTP time server
If you are using a control system, the device automatically synchronizes the
date and time with the control system. If you would like to use an SNTP time
server, you must set the required parameters.
For more information, refer to the information in the section Setting the de-
vice time [
7.5 Name plate
You can enter the data of the nameplates from the transformer, on-load tap-
changer and motor-drive unit and display it later.
When operating ETOS® with the MSENSE® VAM option, you must enter
the correct serial number for every on-load tap-changer. This entry is neces-
sary to ensure the correct assignment of the vibro-acoustic records in the
external database.
7.5.1 Enter the name plate data
You can enter the name plate data for the transformer, the on-load tap-
changer and the motor-drive unit.
Figure 51: Nameplate
Содержание MSENSE VAM
Страница 1: ...Monitoring system MSENSE VAM Operating Instructions 6796573 02 EN ...
Страница 172: ......
Страница 173: ......