Delay time limit value
You can use this parameter to set the delay time. If a limit value is violated,
the device only undertakes the set behavior once the delay time has
elapsed. The purpose of the delay time is to allow the device to ignore brief
limit value violations.
Number of tap change operations
The device's operations counter is automatically increased with every tap-
change operation. You can use this parameter to set the number of tap-
change operations, for example for comparison with the operations counter
of the motor-drive unit.
To set tap position monitoring or the number of tap position changes, pro-
ceed as follows:
1. Go to
Settings > Parameters > Tap position monitoring
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
8.7.11 SCADA
The following section describes how you can configure the device to connect
to a control system (SCADA). You can download the data points with the
help of the export manager.
8.7.11.1 Configuring IEC 61850 (optional)
If you want to use the IEC 61850 control system protocol, you must set the
following parameters. Also refer to the section Configuring the network
[
Figure 81: IEC 61850