3 IT security
Maschinenfabrik Reinhausen GmbH 2021
18
6796573/02 EN
MSENSE
®
VAM
Interface
Protocol
Port
Description
CAN 1
-
-
Connection of the DIO assembly
CAN 2
-
-
Communication with other ISM® devices
(e.g. parallel operation)
COM 1
-
-
Internal system interface
COM 2
-
-
Serial interface (SCADA)
USB
-
-
Import or export of data
ETH 1
TCP
80
HTTP for web-based visualization
1), 2)
ETH 1
TCP
443
HTTPS for web-based visualization
1), 2)
ETH 1
TCP
102
IEC 61850
ETH 1
TCP
502
Modbus
3)
ETH 1
TCP
20000
DNP3
3)
ETH 2.x
TCP
21
FTP
1)
(only for MR service)
ETH 2.x
TCP
80
HTTP for web-based visualization
1)
ETH 2.x
TCP
443
HTTPS for web-based visualization
1)
ETH 2.x
TCP
990
FTPS (only for MR service)
ETH 2.x
TCP
8080
HTTP for web-based visualization
1)
ETH 2.x
TCP
8081
HTTPS for web-based visualization
1)
Table 6: Interfaces and open ports of the CPU assembly
1)
Port is closed if you activate the device's SSL encryption.
2)
Depending on the setting of the parameter Visualization release.
3)
Default setting; if you have modified the port for the control system proto-
col, only the set port is opened.
Encryption standards
The device supports the following TLS versions:
▪ TLS 1.0
▪ TLS 1.1
▪ TLS 1.2
Содержание MSENSE VAM
Страница 1: ...Monitoring system MSENSE VAM Operating Instructions 6796573 02 EN ...
Страница 172: ......
Страница 173: ......