4 Product description
Maschinenfabrik Reinhausen GmbH 2021
21
6796573/02 EN
MSENSE
®
VAM
ETOS® ED/TD with MSENSE® VAM option: Integration solution in the
motor-drive unit
▪ VI 4 vibration sensor input module
▪ VAM sensor assembly (including VS 1 vibration sensor, adapter screw
and kick guard)
▪ Sensor cable for VS 1 vibration sensor
▪ Optional: MC 2-2 media converter
▪ Optional: SW 3-3 media converter with managed switch
▪ Optional: Display
▪ Optional: PT100 for OLTC oil temperature (temperature pocket must be
available in the on-load tap-changer head cover)
1)
ETOS® IM with MSENSE® VAM option: Integration solution in the
customer control cabinet (pluggable modules)
▪ VI 4 vibration sensor input module
▪ VAM sensor assembly (including VS 1 vibration sensor, adapter screw
and kick guard)
▪ Sensor cable for VS 1 vibration sensor
▪ Analog AIO 2 or AIO 4 inputs/outputs
▪ G1 PULS DIMENSION QS3.241 power supply
▪ Digital DIO 28-15 or DIO 42-20 inputs/outputs
▪ CPU II (central processing unit)
▪ Optional: MC 2-2 media converter
▪ Optional: SW 3-3 media converter with managed switch
▪ Optional: Display
▪ Optional: PT100 for OLTC oil temperature (temperature pocket must be
available in the on-load tap-changer head cover)
1)
1)
Oil temperature recording is a prerequisite for the self-learning of the yel-
low limit value curve. As an alternative to recording the OLTC oil tempera-
ture, the top-oil temperature can be used.
4.3 Function description
The product is a monitoring system for monitoring vibro-acoustic signals
from on-load tap-changers. You can use the product to detect time and am-
plitude anomalies in the vibro-acoustic signal progression and receive event
messages when anomalies are detected.
The on-load tap-changer is equipped with measuring equipment that records
the vibro-acoustic signal in the system throughout the entire tap change se-
quence and analyses it immediately upon completion. In addition, the sys-
tem determines the changed tap position and the oil temperature in the on-
load tap-changer.