8 Operation
Maschinenfabrik Reinhausen GmbH 2021
131
6796573/02 EN
MSENSE
®
VAM
The following information is displayed in tabular form for configuring the ana-
log inputs and outputs. Grayed out elements cannot be changed.
Property
Options
Function
Function of the analog input (I: ...) or the analog output (O: ...). You
can adjust the designation.
Card/channel
Select the slot and channel of the analog sensor. Note the connec-
tion diagram supplied.
Signal type
Select signal type of analog sensor or deactivate analog output.
▪ 4...20 mA
▪ PT100-2/3/4, PT1000-2/3/4
Min/Max
1)
Set the minimum and maximum values of the sensor, e.g. with a
4...20 mA signal, the corresponding measured value for 4 mA and
the corresponding value for 20 mA.
Table 36: Configuration of the analog inputs and outputs
Figure 95: Configuring analog inputs/outputs
The operation described below is only possible if you access the visualiza-
tion using a computer. You can only change the configuration of the analog
inputs and outputs if you have a Parameter Configurator or Administrator
role.
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin
Creating a backup
You need to create a backup to be able to reset the system in the event that
any incorrect configuration settings are made. To do so, proceed as follows:
1. Go to
Settings > Export
.
2. Go to the option
Settings
to export a backup copy of the current settings.
3. Select the desired
Interface
(USB or PC).
4. Press the
Export
button to start the export.