8 Operation
Maschinenfabrik Reinhausen GmbH 2021
135
6796573/02 EN
MSENSE
®
VAM
8.15.1.3 Function modules
TPLE provides various function modules for processing the information.
8.15.1.3.1 AND
Description
AND, logical AND link
Inputs
Input 1…4 (BOOL)
Outputs
Output (BOOL)
Parameter
None
Function
If all configured inputs are TRUE, the output is TRUE,
otherwise it is FALSE.
Initial state
All inputs and outputs are FALSE.
Non-configured inputs are assumed to be TRUE.
If no input is configured, the module is not run so it re-
mains in its initial state.
Table 37: AND function module
8.15.1.3.2 NAND
Description
NAND, logical NOT-AND link
Inputs
Input 1…4 (BOOL)
Outputs
Output (BOOL)
Parameter
None
Function
If all configured inputs are TRUE, the output is FALSE,
otherwise it is TRUE.
Initial state
All inputs and outputs are FALSE.
Non-configured inputs are assumed to be TRUE so
that they have no impact on the output.
If no input is configured, the output therefore remains in
the initial state of FALSE.
Table 38: NAND function module
8.15.1.3.3 OR
Description
OR, logical OR link
Inputs
Input 1…4 (BOOL)
Outputs
Output (BOOL)
Parameter
None
Function
If one of configured inputs is TRUE, the output is
TRUE, otherwise it is FALSE.
Initial state
All inputs and outputs are FALSE.
Non-configured inputs are assumed to be FALSE.
Table 39: OR function module