8 Settings via the MICT
Rev. 08/2018
61
RS485
Via the field
RS485
, deactivate or activate the RS485 interface of the device.
–
RS485 Settings
–
Baudrate
Select the desired data transfer rate from the list. The Modbus baud rate can be defined
between 9600 bit/s and 115200 bit/s, the recommended value being 19200 bit/s.
–
Parity
Define if a parity bit is used and if the parity is to be even or odd.
–
Stopbits
Determine if one or two stop bits are to be sent. Two stop bits can only be sent if no
parity has been selected.
–
Modbus Settings
–
Modbus Address
The Modbus address can be assigned between 1 and 247. Note that IDs cannot be
assigned more than once.
–
Mode
Define if the data are transferred in the ASCII or RTU mode.
Setting the transfer rate
Please note that all devices connected with a bus must be set to the same
transfer rate.