![Motortech VariStep3 Скачать руководство пользователя страница 58](http://html1.mh-extra.com/html/motortech/varistep3/varistep3_operating-manual_1839329058.webp)
8 Settings via the MICT
58
Rev. 08/2018
Settings of the input selected
Analog Inputs (Current or Voltage)
Based on the values used by your master control, you can define the values
of the Open and the Close position for the analog inputs in the MICT. The
value applied to the input is then converted proportionally to the values
entered in a corresponding opening angle of the throttle or the fuel ring of
the VariFuel2.
Example:
Your master control works with a current input of 4 mA to 20 mA. In the
MICT, you configure 4 mA to refer to the closed position and 20 mA to the
open position. If the current on the input is now 16 mA, the opening is 75 %.
Binary inputs
In the MICT, enter the settings for the binary inputs
Dir
and
Steps
. The level
on the
Dir
determines the direction in which the fuel ring of the VariFuel2 or
the throttle will move if there are pulses on the
Steps
.
Example:
You have selected the option
High -> Open
in the MICT under
Direction
. If a
high level is applied on the
Dir
, with each pulse on the
Steps
one step is
added to the current position. The fuel ring or throttle will then move
gradually from the Closed to the Open direction.
Unused inputs and outputs
Please note that the terminals for the analog inputs and outputs not
selected in the MICT must remain unoccupied.