4 Product Description
Rev. 08/2018
23
Status signaling
The status of the VariStep3 stepper motor driver is signaled via the LED
Status
.
–
Flashing
green
: Error-free operation
–
Flashing
orange
: Warning
Warnings can be acknowledged by simultaneous pressing of buttons
Open
and
Close
(in manual Mode) or by the external reset signal.
Warnings can for example be caused by:
–
Overload of the device
In addition, the LED flashes orange for the following reasons.
–
No device type has been configured (device type:
None
or
Unknown
).
–
Device connected was changed.
–
Overtemperature or over current error confirmed by MICT.
–
A reference run is required.
The first two cases make downloading a modified configuration to the
device a priority.
–
Flashing
red
: Error
Errors can be acknowledged by simultaneous pressing of buttons
Open
and
Close
or by the external reset signal. Errors can for example be
caused by:
–
Step loss
–
Overtemperature
–
Low voltage
–
Over current
–
Alternate flashing of
red
and
green
:
The supply voltage for the device was too low during start up.