8 Settings via the MICT
Rev. 08/2018
57
–
Output
Select the analog output that is to be used by the master control connected.
–
External manual/automatic selection enabled
Disable the check box to deactivate the
Manual/Auto
switch on the stepper motor driver.
The stepper motor driver may then only be put in manual mode via the MICT with the
corresponding authorization.
Input Voltage/Input Current
Depending on which input is selected, you have different adjustment options available. For the
analog inputs, enter the values for the open and closed position of the fuel ring. Here, please
adhere to the following values:
–
Input voltage: 0 V to 10 V
–
Input current: 0 mA to 20 mA
Click this button to apply the settings of the analog input (current or voltage) to the output
selected. If you have selected another input as output (e. g. input: current; output: voltage), the
adjusted values are converted in accordance with the output's value range.
Input Step Count/Step Count Configuration
Define both the
Direction
and the
Init Position
of the steps of the binary inputs. The initial
position (=Init Position) will be approached after the reference run of the stepper motor.
To make these settings, refer to all additional information as provided in the following note.
Output Voltage/Output Current
Depending on the selection, enter the relevant current or voltage values, which are to
correspond to the open and closed position. Here, the same value ranges are applicable as with
the analog inputs.