302
function, you need to select
ModbusRTU
, select
CRC16 (MOMS-DBU SRTU)
, and set the start byte
to
1
. After the auto CRC check function is enabled, do not enter CRC information in commands.
Otherwise, command errors may occur due to repeated CRC check.
The commissioning command to set the inverter whose address is 03H to be forward running is as
follows:
Note:
1. Set the address (P14.00) of the inverter to 03.
2. Set "Channel of running commands" (P00.01) to "Communication", and set "Communication
channel of running commands" (P00.02) to the Modbus communication channel.
3. Click
Send
. If the line configuration and settings are correct, a response transmitted by the inverter
is received as follows:
9.5
Common communication faults
Common communication faults include the following:
•
No response is returned.
•
The inverter returns an exception response.
Possible causes of no response include the following:
•
The serial port is set incorrectly. For example, the converter uses the serial port COM1, but
COM2 is selected for the communication.
•
The settings of the baud rates, data bits, end bits, and check bits are inconsistent with those set
on the inverter.
•
The positive pole (+) and negative pole (-) of the RS485 bus are connected reversely.
•
The resistor connected to 485 terminals on the terminal block of the inverter is set incorrectly.
Содержание MSI350 Series
Страница 1: ...MSI350 SERIES INVERTER USER MANUAL...
Страница 2: ...2...
Страница 34: ...34 4 2 6 Vertical installation Fig 4 5 Vertical installation...
Страница 38: ...38 Fig 4 10 3PH 380V 30 37kW Fig 4 11 3PH 380V 45 110kW Fig 4 12 660V 22 45kW...
Страница 39: ...39 Fig 4 13 660V 55 132kW Fig 4 14 380V 132 200kW and 660V 160 220kW...
Страница 40: ...40 Fig 4 15 380V 220 315kW and 660V 250 355kW...
Страница 71: ...71...
Страница 83: ...83 When selecting customized V F curve function users can set the reference channels and...
Страница 90: ...90...
Страница 96: ...96...
Страница 101: ...101...
Страница 147: ...147...
Страница 260: ...260 7 6 Analysis on common faults 7 6 1 Motor fails to work...
Страница 261: ...261 7 6 2 Motor vibrates...
Страница 262: ...262 7 6 3 Overvoltage...
Страница 263: ...263 7 6 4 Undervoltage...
Страница 264: ...264 7 6 5 Unusual heating of motor...
Страница 265: ...265 7 6 6 Inverter overheating...
Страница 266: ...266 7 6 7 Motor stalls during ACC...
Страница 267: ...267 7 6 8 Overcurrent...
Страница 318: ...318 The following figure shows the external wiring of the extension card used in combination with a push pull encoder...
Страница 336: ...336 A 6 5 PROFINET communication card EC TX509...
Страница 339: ...339 A 7 Programmable extension card function description A 7 1 Programmable extension card EC PC501 00...
Страница 380: ...380...
Страница 386: ...386...
Страница 387: ...387...
Страница 388: ...388...