7.7 Countermeasures on common interference
7.7.1
Interference on meter switches and sensors
Interference phenomenon
Pressure, temperature, displacement, and other signals of a sensor are collected and displayed by a
human-machine interaction device. The values are incorrectly displayed as follows after the inverter is
started:
1. The upper or lower limit is wrongly displayed, for example, 999 or -999.
2. The display of values jumps (usually occurring on pressure transmitters).
3. The display of values is stable, but there is a large deviation, for example, the temperature is
dozens of degrees higher than the common temperature (usually occurring on thermocouples).
4. A signal collected by a sensor is not displayed but functions as a drive system running feedback
signal. For example, an inverter is expected to decelerate when the upper pressure limit of the
compressor is reached, but in actual running, it starts to decelerate before the upper pressure limit
is reached.
5. After an inverter is started, the display of all kinds of meters (such as frequency meter and current
meter) that are connected to the analog output (AO) terminal of the inverter is severely affected,
displaying the values incorrectly.
6. Proximity switches are used in the system. After an inverter is started, the indicator of a proximity
switch flickers, and the output level flips.
Solution
1. Check and ensure that the feedback cable of the sensor is 20 cm or farther away from the motor
cable.
2. Check and ensure that the ground wire of the motor is connected to the PE terminal of the inverter
(if the ground wire of the motor has been connected to the ground block, you need to use a
multimeter to measure and ensure that the resistance between the ground block and PE terminal
is lower than 1.5
Ω
).
3. Try to add a safety capacitor of 0.1
μ
F to the signal end of the feedback signal terminal of the
sensor.
4. Try to add a safety capacitor of 0.1
μ
F to the power end of the sensor meter (pay attention to the
voltage of the power supply and the voltage endurance of the capacitor).
5. For interference on meters connected to the AO terminal of an inverter, if AO uses current signals
of 0 to 20 mA, add a capacitor of 0.47
μ
F between the AO and GND terminals; and if AO uses
voltage signals of 0 to 10 V, add a capacitor of 0.1
μ
F between the AO and GND terminals.
Содержание MSI350 Series
Страница 1: ...MSI350 SERIES INVERTER USER MANUAL...
Страница 2: ...2...
Страница 34: ...34 4 2 6 Vertical installation Fig 4 5 Vertical installation...
Страница 38: ...38 Fig 4 10 3PH 380V 30 37kW Fig 4 11 3PH 380V 45 110kW Fig 4 12 660V 22 45kW...
Страница 39: ...39 Fig 4 13 660V 55 132kW Fig 4 14 380V 132 200kW and 660V 160 220kW...
Страница 40: ...40 Fig 4 15 380V 220 315kW and 660V 250 355kW...
Страница 71: ...71...
Страница 83: ...83 When selecting customized V F curve function users can set the reference channels and...
Страница 90: ...90...
Страница 96: ...96...
Страница 101: ...101...
Страница 147: ...147...
Страница 260: ...260 7 6 Analysis on common faults 7 6 1 Motor fails to work...
Страница 261: ...261 7 6 2 Motor vibrates...
Страница 262: ...262 7 6 3 Overvoltage...
Страница 263: ...263 7 6 4 Undervoltage...
Страница 264: ...264 7 6 5 Unusual heating of motor...
Страница 265: ...265 7 6 6 Inverter overheating...
Страница 266: ...266 7 6 7 Motor stalls during ACC...
Страница 267: ...267 7 6 8 Overcurrent...
Страница 318: ...318 The following figure shows the external wiring of the extension card used in combination with a push pull encoder...
Страница 336: ...336 A 6 5 PROFINET communication card EC TX509...
Страница 339: ...339 A 7 Programmable extension card function description A 7 1 Programmable extension card EC PC501 00...
Страница 380: ...380...
Страница 386: ...386...
Страница 387: ...387...
Страница 388: ...388...