What it Means
What to Do
Error Message
SYS INIT
The system is completing initialization
The configuration stored in non-volatile
memory is invalid
User has reconfigured the unit with an
illegal configuration
A specific wire was detected as broken
Undetermined wire broken
Input saturation condition (input reached
110% of calibrated range)
Input has gone outside the legal range
(as defined by the input LRV and URV
by more than 1%)
Calibration data is bad
Wait. Operation should commence in a few
seconds.
Using the menu system, trigger the unit to use the
FCTRY CONFG selection in the options menu
causing it to reset to factory configuration. Next
configure as appropriate for the application.
Usually caused by changing the input range, or
scaled range such that the trip points and/ or
deadband settings have become illegal.
Reconfigure with legal values.
Repair the broken wire(s), and use the menu
system to RESET FAULTS or MR Terminal (if
configured) or cycle power.
Check the input signal to ensure that it is within
the sensor limits and use the menu system to
RESET FAULTS or MR Terminal (if configured) or
cycle power.
Check the input and/or the input Upper and Lower
Range settings and use the menu system to
RESET FAULTS or MR Terminal (if configured) or
cycle power.
These errors are generated by internal
diagnostics (see STA Diagnostics and Fault
Alarms p7). Spurious errors that could be caused
by external factors like transients or surges, may
result in a diagnostic failure and trigger the fault
alarm. Cycle power to the unit to clear the latched
fault alarm. If the error persists, then please
record the error message and contact Moore
Industries Customer Support for further
assistance.
ERROR CKSUM
ERROR CONFIG
WIREn BROKE
WIRES BROKE
ERROR INSAT
ERROR OOR
ERROR CALIB
General ADC failure
ERROR ADC _ _ *
Fault alarm failure
ERROR RLAYF
Trip alarm 1 hardware failure
ERROR RLAY1
Trip alarm 2 hardware failure
ERROR RLAY2
General software failure detected by
diagnostics
General hardware failure detected by
diagnostics
Factory information is bad
ERROR FCTRY/
INFO
Table 6.1.
STA Diagnostic messages and corrective actions messages
* Error messages ERROR ADC, ERROR SW, and
ERROR HW will also include a 2 or 3 digit suffix. Moore
Industries Customer Service Technicians will use these codes to
help determine the origin of the error.
Note:
The Manual Reset (MR) will only reset Input Faults if configured in the Alarms Menu.
Maintenance
Moore Industries recommends that the calibration of this instrument should be checked every
year and re-calibrated only when necessary. In addition, we suggest a quick check for terminal
tightness and general unit condition. Always adhere to any site requirements for programmed
maintenance.