Programmable Current/Voltage Safety Trip Alarm
STA
HLPRG
SEC
TION 4
Scaling the Analog Output
(-AO Option)
Figure 4.8 gives an overview of the Analog Output Scaling menu.
Follow these instructions to scale the analog output after you have performed the configuration.
Note:
When using the front panel pushbuttons to enter your scaling values, you may enter only
values to two decimal places (hundredths).
1. At the “SCALE AOUT” display, press
SELECT
.
2. Press
SELECT
at the “AOUT ZERO” parameter and enter the value you want to output
when your input is at zero. Select from 0.00 to 21.6mA or -0.20 to 10.5V (default is 4mA
or 0V) then press
SELECT.
WARNING:
The Analog Output Zero must be set to 4mA for a safety function.
3. Press
SELECT
at the “AOUT FULL” screen. Enter the value you want to output when
your input is at full scale. Select from 0.00 to 21.6mA or -0.20 to 10.5V (default is 20mA or
10V) then press
SELECT.
4. “EXIT SCALE” appears. If all scaling parameters have been set, press
SELECT.
Note:
Analog Output can be reversed, in which case the Zero value will be greater than the Full
value. In either case there needs to be a minimum Span of 4mA or 1V.
Figure 4.8.
SCALE AOUT Menu