Programmable Current/Voltage Safety Trip Alarm
STA
HLPRG
SEC
TION 4
Trimming the Analog Output
(-AO Option)
Figure 4.9 gives an overview of the Analog Output Trimming menu.
Output trimming increases the measurement accuracy of the STA by calibrating its analog output
to the device that is receiving the output. This ensures that the instrument is being correctly
interpreted.
Connect the unit as shown in Figure 4.10 and allow five minutes for warm up and stabilization.
1. At the “TRIM AOUT” display, press
SELECT
.
2. “TRIM ZERO” appears. Press
SELECT
. The value 0.00 (mA or V depending on the set
up) is shown. While monitoring your reading on the meter, use the
UP
and
DOWN
buttons
to adjust the output to the desired level. Use the meter in the set up to monitor the output
as it is adjusted. Press
SELECT
when the output is set as desired.
Note:
The value on the LCD is an adjustment to the AOUT ZERO or FULL value. This
adjustment is limited to 10% of span.
3. Press
SELECT
at “TRIM FULL” and repeat Step 2. Press
SELECT
. “FCTRY TRIM” is
shown on the display.
4. If you wish to
reset
the user-configured trimming values and use factory trimming, press
SELECT
at the “FCTRY TRIM” screen. Use the
UP
and
DOWN
buttons to choose “YES”;
press
SELECT
. “TEST AOUT” is brought up on the display.
By selecting “NO” at the “FCTRY TRIM” screen, the user-configured trim values will be
used.
5. In order to check output performance and accuracy, you may want to perform an output
test. If you choose to enable this test, follow the instructions in Step 6. To bypass this
feature, use the
DOWN
button and scroll to “EXIT TRIM”.
6. To enable the analog output test, press
SELECT
at the “TEST AOUT” display. Use the
UP
and
DOWN
buttons to set your output test value and press
SELECT
. “EXIT TRIM”
appears; press
SELECT.