Programmable Current/Voltage Safety Trip Alarm
STA
HLPRG
SEC
TION 4
Configuring the Options
Figure 4.11 gives an overview of the Options Configuration menu.
You may configure and test the display, select the 50/60Hz filter, add a startup delay and reset to
factory defaults from this menu.
To configure STA options, follow the steps below.
1. At the “CONFG OPTNS” screen, press
SELECT.
2. “DSPLY MODE” appears. Press
SELECT
to enter the menu. Choose between “PV”,
“AOUT” and “PV + AOUT” by using the
UP
or
DOWN
buttons. Press
SELECT.
3.
Next, the “SET DPS” display appears. Press
SELECT.
Scroll through the available
choices by using the
UP
or
DOWN
buttons and press
SELECT
once you have made your
selection.
4. “SET FILTR” appears; press
SELECT
. Here, you must select the proper line frequency of
your AC source–50Hz or 60Hz; press
SELECT
.
5 “START DELAY” appears; press SELECT. Here the desired startup delay can be entered
by using the
UP
or
DOWN
buttons. This adds a delay after the STA has been initialized
to allow the process input to stabilize. During initialization and delay all outputs are held
in their failsafe mode. When the desired delay in seconds is displayed, press SELECT.
START DELAY default is 0 seconds.
Note
: For STA units with firmware versions 1.5 and earlier, the start up delay is not configurable
and is set to 0.
6. “DSPLY TEST” appears; press
SELECT
. Display test is executed and iterates through
five different character patterns (this ensures all LCD segments function properly).
7. “FCTRY CONFG” appears. Press
SELECT
Using the
UP
or
DOWN
buttons choose
between “RESET NO?” and “RESET YES?”; press SELECT.
Note:
When resetting unit to factory default, refer to the Quick Set-Up Guide on Pg. 5 for default
values.
8. “EXIT OPTNS” appears. Press
SELECT.
Proceed to the “CONFG PASWD” menu.