www.miinet.com
Moore Industries-International, Inc.
- 6 -
User’s Manual
225-748-01L
February 2017
Default/Factory Configuration
The following are the default factory settings for your unit.
Input:
4-20mA
*Lower Out of Range Value:
3.84 mA (1% of Span)
*Upper Out of Range Value:
20.16 mA (1% of Span)
*Startup Delay:
0 Seconds
Scale Mode:
Off
Trim Mode:
Factory Trim
Trip Alarms:
Trip High at 12mA with Deadband set to 0
*Input Fault Alarm:
Latching (On)
*Manual Reset:
Trip Alarms 1 & 2 Only
Optional Analog Output (AO):
Current, No Damping, Fail Low, Scaled to 4-20mA
Display:
Process Variable (PV), Auto Decimal Point, 60Hz Filter
Broken Wire Detection:
Level Set to 0 (disabled)
Password:
1
* For STA units with firmware versions 1.5 and earlier, these Settings are not configurable.
Programmable Current/Voltage Safety Trip Alarm
STA
HLPRG
SEC
TION 1