Programmable Current/Voltage Safety Trip Alarm
STA
HLPRG
SEC
TION 4
Configuration Exit
Figure 4.14 gives an overview of the Confg Exit menu.
1. At “CONFG EXIT”, press
SELECT
.
2. If no error is present use the
UP
and
DOWN
buttons between “SAVE NO?” and “SAVE
YES?”.
3. If “SAVE NO?” is selected, you will be returned to View menu and no changes will be
applied to unit (previous configuration will remain unchanged).
4. If “SAVE YES?” is selected, you will be returned to View menu and changes will be applied
to unit and stored in non-volatile memory.
5. If error is present two options are available “ERROR LIST” and “ERROR UNDO”. Use the
UP
and
DOWN
buttons to cycle these two options.
6. If “ERROR LIST” is selected, you see the list of configuration errors, press
SELECT
and
this will return you to the Main menu to make changes where needed.
7. If “ERROR UNDO” is selected, you will be returned to View menu and no changes will be
applied to unit (previous configuration will remain unchanged).
Figure 4.14.
CONFG EXIT Menu
CONFG
EXIT
VIEW
MENU
ENTER
PASS
ENTER
XXX
Selection:
ERROR LIST?
ERROR UNDO?
SEL LIST
SEL UNDO
SEL
SEL (no error)
SEL
CONFG
INPUT
SEL (error)