![Moeller S40-AM-TL Скачать руководство пользователя страница 90](http://html1.mh-extra.com/html/moeller/s40-am-tl/s40-am-tl_manual_1819282090.webp)
Example
87
10/00 AWB27-1301-GB
Secondary station 1 (PS4-200)
Variable declaration “TCMT3_UT”
VAR_INPUT
acd_subaddress : USINT(0..0);
ACD subaddresses
acd_offset
: USINT(0..15);
ACD offset addresses
acd_length
: USINT(1..16);
User data length for ACD data
fixed_length
: USINT(1..16);
User data length for fixed length frames
tra_dat
: ARRAY[0..0, 0..15] OF BYTE;
Send data array (subaddresses, offset
addresses)
END_VAR
VAR_OUTPUT
rec_dat
: ARRAY[0..0, 0..15] OF BYTE;
Receive data array
(subaddresses, offset addresses)*)
END_VAR
VAR_IN_OUT
TCM_tdata
: ARRAY[1..36] OF BYTE;
Base address for send data
TCM_rdata
: ARRAY[1..36] OF BYTE;
Base address for receive data
END_VAR
VAR CONSTANT
rts_select
: BOOL:= 0;
RTS switched/static-on
tra_sub_max
: UINT:= 0;
Transmit max. subaddress
rec_sub_max
: UINT:= 0;
Receive max. subaddress
tra_dfl_max
: UINT:= 16;
Transmit length of data array
rec_dfl_max
: UINT:= 16;
Receive length of data array
time_tout
: TIME:= T#10s;
Protocol monitoring time
rts_delay_on
: TIME:=T#10ms;
RTS on-delay
rts_delay_off
: TIME:=T#30ms;
RTS off-delay
cts_gap_time
:TIME:=T#0ms;
CTS timeout gap_time
END_VAR
Содержание S40-AM-TL
Страница 7: ...10 00 AWB27 1301 GB 4 ...
Страница 9: ...6 10 00 AWB27 1301 GB ...
Страница 13: ...10 10 00 AWB27 1301 GB ...
Страница 55: ...Basic Function Blocks 52 10 00 AWB27 1301 GB ...
Страница 103: ...100 10 00 AWB27 1301 GB ...
Страница 107: ...104 10 00 AWB27 1301 GB ...
Страница 113: ...10 00 AWB27 1301 GB 110 ...