Service 30: Remote reset
When service 30 is executed, the function block of the polled
secondary station is returned to its basic status (the error
counters and frame sequence bit are set to “0”).
Service 31: Read status
When service 31 is executed, parameters and error counters
are transferred from the polled secondary station to the
primary station, where they are indicated at function block
outputs.
Figure 24: Service 31: Read status
rem_stationaddress
fixed_length
rem_ctrat
rem_crect
rem_cperr
rem_cterr
rem_clerr
rem_cserr
rem_stationaddress
fixed_length
rem_ctrat
rem_crect
rem_cperr
rem_cterr
rem_clerr
rem_cserr
RAM
Primary station
RAM
Secondary station