Warning!
Dangerous electrical voltage!
Before commencing the installation
●
Disconnect the power supply of the
device.
●
Ensure that devices cannot be
accidentally restarted.
●
Verify isolation from the supply.
●
Earth and short circuit.
●
Cover or enclose neighbouring units that
are live.
●
Follow the engineering instructions
(AWA) of the device concerned.
●
Only suitably qualified personnel in
accordance with EN 50 110-1/-2
(VDE 0105 Part 100) may work on this
device/system.
●
Before installation and before touching
the device ensure that you are free of
electrostatic charge.
●
The functional earth (FE) must be
connected to the protective earth (PE) or
to the potential equalisation. The system
installer is responsible for implementing
this connection.
●
Connecting cables and signal lines
should be installed so that inductive or
capacitive interference do not impair the
automation functions.
●
Install automation devices and related
operating elements in such a way that
they are well protected against
unintentional operation.
●
Suitable safety hardware and software
measures should be implemented for the
I/O interface so that a line or wire
breakage on the signal side does not
result in undefined states in the
automation devices.
●
Ensure a reliable electrical isolation of
the low voltage for the 24 volt supply.
Only use power supply units complying
with IEC 60 364-4-41 (VDE 0100
Part 410) or HD 384.4.41 S2.
●
Deviations of the mains voltage from
the rated value must not exceed the
tolerance limits given in the speci-
fications, otherwise this may cause
malfunction and dangerous operation.
●
Emergency stop devices complying with
IEC/EN 60 204-1 must be effective in all
operating modes of the automation
devices. Unlatching the emergency-stop
devices must not cause restart.
●
Devices that are designed for mounting
in housings or control cabinets must only
be operated and controlled after they
have been installed with the housing
closed. Desktop or portable units must
only be operated and controlled in
enclosed housings.
●
Measures should be taken to ensure the
proper restart of programs interrupted
after a voltage dip or failure. This should
not cause dangerous operating states
even for a short time. If necessary,
emergency-stop devices should be
implemented.
●
Wherever faults in the automation
system may cause damage to persons
or property, external measures must be
implemented to ensure a safe operating
state in the event of a fault or malfunction
(for example, by means of separate limit
switches, mechanical interlocks etc.).
Содержание S40-AM-TL
Страница 7: ...10 00 AWB27 1301 GB 4 ...
Страница 9: ...6 10 00 AWB27 1301 GB ...
Страница 13: ...10 10 00 AWB27 1301 GB ...
Страница 55: ...Basic Function Blocks 52 10 00 AWB27 1301 GB ...
Страница 103: ...100 10 00 AWB27 1301 GB ...
Страница 107: ...104 10 00 AWB27 1301 GB ...
Страница 113: ...10 00 AWB27 1301 GB 110 ...