Basic Function Blocks
50
10/00 AWB27-1301-GB
Parameter assignment of TCMT3_BT
Procedure
The exchange of data is started by a rising edge at the
“strobe” input of function block “TCMT2_BS” in the primary
station. The primary station sends 8 bytes of user data from
the “tra_dat” array in FT3 frame format to secondary
station 1. The secondary station receives this data and stores
it in the “rec_dat” receive data array. Upon receipt,
secondary station 1 sends 8 bytes of user data from its send
data array “tra_dat” to the primary station, which stores the
data in its receive data array “rec_dat”.
CAL FW_TLBS(
reset:=,
Resets the function block
local_stationaddress:=x,
Station address of station 1: x = 1, station 2: x = 2
user_status_1:=,
User status bit 1
user_status_2:=,
User status bit 2
user_status_3:=,
User status bit 3
user_status_4:=,
User status bit 4
baudrate:=1200,
Transmission speed
watchdog_time:=,
Monitoring speed of communication
fixed_length:=8,
User data length for fixed length frames
tra_dat:=,
Send data array
TCM_tdata:=,
Base address for send data
TCM_rdata:=
Base address for receive data
|
:=active,
Indicates that a service is being processed.
:=result,
Result becomes active after a falling edge at the output.
Result = 0: Error, Result = 1: OK
:=dcd,
Indicates the status of the transmission route.
:=watchdog,
Monitoring time procedure
:=fail_code,
Error code
:=rec_dat)
Receive data array
Содержание S40-AM-TL
Страница 7: ...10 00 AWB27 1301 GB 4 ...
Страница 9: ...6 10 00 AWB27 1301 GB ...
Страница 13: ...10 10 00 AWB27 1301 GB ...
Страница 55: ...Basic Function Blocks 52 10 00 AWB27 1301 GB ...
Страница 103: ...100 10 00 AWB27 1301 GB ...
Страница 107: ...104 10 00 AWB27 1301 GB ...
Страница 113: ...10 00 AWB27 1301 GB 110 ...