4 SETTINGS AND PROCEDURES PRIOR TO OPERATION
4.2 Settings and Procedures Prior to Starting the Operation
The following shows a flow of the procedure that is required prior to operating:
Procedures prior
to operation
Create a program for each communication
Operation
See Section 4.4, "Connecting
to the Network."
See Section 4.5, "Settings from
Ethernet Parameters."
See Section 5.4, "Confirming the Completion
of the Initial Processing."
See applicable
communication function
Connect the Ethernet module to the base module and
wire the 24VDC power supply.
Connect the Ethernet module to the Ethernet network.
Send the "Ping" command from an external device and
confirm the completion of the Ethernet module initial
processing
Setting the Ethernet module network parameters .
POINT
(1) When the parameter settings are added or modified using the FX
Configurator-EN (GX Developer), the settings differs depending on the
connection condition to the Ethernet module as shown below.
•
When directly connected to the PLC
After the parameter settings are added or modified, re-initialization
processing can be automatically performed.
•
When connected via Ethernet
The added or modified parameter settings are not reflected.
To operate the Ethernet module after the parameter settings are added or
modified with FX Configurator-EN (GX Developer), first save the parameter
values, second reboot the Ethernet’s module power.
(2) Timing for powering ON
Power ON the PLC and the Ethernet module with the timing as shown below.
ON
ON
OFF
Power OFF at the same time
or the Ethernet afterwards.
PLC
Ethernet
module
Power ON at the same
time or the Ethernet first.
OFF