3 - 18 3 - 18
MELSEC-F
3 SPECIFICATIONS
(e) Router relay parameter setting area (BFM #512 to 1599)
BFM number
Decimal
(Hexadecimal)
Attribute Application
Name
Initial value
Decimal
(Hexadecimal)
Flash ROM
save
Reference
section
512 to 513
(200 to 201
H
)
R/W Sub-net
mask
514 to 515
(202 to 203
H
)
R/W
Default router IP address
0
(0
H
)
Section 5.3
516 to 1599
(204 to 63F
H
)
Router relay
parameter
setting area
System area
(f) Open/close control (BFM #1600 to 1663)
BFM number
Decimal
(Hexadecimal)
Attribute Application
Name
Initial value
Decimal
(Hexadecimal)
Flash ROM
save
Reference
section
1600
(640
H
)
R/W
Re-
initialization
• Write value
Re-initialization request
0001H : Re-initialization ([COM.ERR.] LED OFF)
0002H : Re-initialization after reading data in Flash ROM
([COM.ERR.] LED OFF)
0005H : Re-initialization ([COM.ERR.] LED retains status.)
0006H : Re-initialization after reading data in Flash ROM
([COM.ERR.] LED retains status.)
• Read value
0008H
: During re-initialization
8000H
: At re-initialization completion
C000H
: At re-initialization error
• In the re-initialization standby, the write value is read directly.
0
(0000
H
)
1601
(641
H
)
R/W
COM.ERR.
Off
[COM.ERR.] Off request
• Write value
0001H: [COM.ERR.] LED Off request
(In standby until extinction)
• Read value
0002H: Stores at normal completion
0001H is read while ready until LED OFF operation starts
0
(0000
H
)
(Continues on the next page)