App - 7 App - 7
MELSEC-F
APPENDIX
(3) FX Configurator-EN (GX Developer) settings
Set the PLC parameters as follows.
(a) Operation settings
Communication data code
: ASC II (BFM#24 b1: ON)
Initial timing
: Always wait for OPEN (Communication
possible at STOP time) (BFM#24 b8: ON)
IP address
: 172.16.56.99 (AC.10.38.63
H
) (BFM#106
to 107)
(b) Open settings
Protocol
: TCP (BFM#32 b8: OFF)
Open system
: Unpassive (BFM#32 b14, b15: 10
H
)
Fixed buffer
: Send (BFM#32 b0: OFF)
Fixed buffer communication
procedure
: Procedure exist (MC) (BFM#32 b9: OFF,
b10: ON)
Pairing open
: Disabie (BFM#32 b7: OFF)
Existence confirmation
: No confirm (BFM#32 b1: OFF)
Host station Port No.
: 10000 (BFM#40)