3 - 11 3 - 11
MELSEC-F
3 SPECIFICATIONS
(Continued from the previous page)
BFM number
Decimal
(Hexadecimal)
Attribute Application
Name
Initial value
Decimal
(Hexadecimal)
Flash ROM
save
Reference
section
28
(1C
H
)
R
Module status area
Stores Ethernet module status
b0: INIT 1: Initial processing normally completed
0: —
b1: System bit
b2: 100M/10M 1: 100Mbps
0: 10Mbps/When not connected
b3: ERR. 1: Setting abnormal display
0: Setting normal display
b4: COM, ERR 1: Communication abnormal display
0: Communication normal display
b5: 1: Initial processing abnormally completed
0: —
b6: 1: Open processing abnormally completed
b7: 1: Link signal ON 0: Link signal OFF
b8: Connection No.1 1: Open 0: Closed
b9: Connection No.2 1: Open 0: Closed
b10: Connection No.3 1: Open 0: Closed
b11: Connection No.4 1: Open 0: Closed
b12: Connection No.5 1: Open 0: Closed
b13: Connection No.6 1: Open 0: Closed
b14: Connection No.7 1: Open 0: Closed
b15: Connection No.8 1: Open 0: Closed
b0 and b5 are cleared at re-initialization request.
b6 is cleared at open request.
0
(0000
H
)
Section 4.3
29
(1D
H
)
R/W Error code storage
Stores the first error code (when the value of this BFM
number is 0000H)
Writing 0000H resets the error.
0
(0000
H
)
Section 11.3
30
(1E
H
)
R
Model name storage
Model name (K7130)
7130
(1BDA
H
)
—
31
(1F
H
)
— System
area
— — —