5 - 26 5 - 26
MELSEC-F
5 COMMUNICATION PROCEDURE
(9) Destination Port No.
(connection numbers 1 to 8; BFM#43, 50, 57, 64, 71, 78, 85, 92)
(a) Set the port numbers of the external devices for each connection in decimal.
(b) The port numbers of the external devices are set in the range from 1025 to
65535.
(c) Set the port numbers for the external device upon consulting a network
administrator.
(d) The following table provides some precautions that should be observed
when setting port numbers.
( in the diagram indicates a device and indicates a port number.)
Communication
protocol
Status of connection establishment
(
: Port (indicates port number))
Description of connection
TCP
UDP
Ethernet module
External device
External device
When connecting to multiple external devices,
set multiple port numbers for the local station.
Ethernet module
External device
External device
When connecting to multiple external devices,
set a single port number for the local station.
(However, it is necessary to open a connection
for each external device)
This cannot be chosen when the local station is
Unpassive.
Ethernet module
External device
When connecting to multiple ports of an external
device, set multiple port numbers for the
Ethernet module.
Ethernet module
External device
When connecting to multiple ports of an external
device, set a single port number for the Ethernet
module. (However, it is necessary to open a
connection for each external device port)
This cannot be chosen when the local station is
Unpassive.
Ethernet module
External device
When connecting to the same port of an external
device, set multiple port numbers for the
Ethernet module. (However, it is necessary to
open a connection for each Ethernet module
port)
Ethernet module
External device
Setting multiple ports numbers for the same port
of an external device and the Ethernet module is
possible only when paring open is set.
Important
Parameters for connections that communicate by Passive open and UDP open
must always be set from this screen when "Always wait for OPEN (communication
possible at STOP time)" is selected in the Operational settings (see Section 4.6).
Содержание FX3U-ENET
Страница 1: ...USER S MANUAL FX3U ENET ...
Страница 2: ......
Страница 159: ...8 6 8 6 MELSEC F 8 COMMUNICATION USING MC PROTOCOL MEMO ...
Страница 295: ...App 25 App 25 MELSEC F APPENDIX MEMO ...
Страница 297: ......