5 - 45 5 - 45
MELSEC-F
5 COMMUNICATION PROCEDURE
Open status
Closed status
Initial normal completion
BFM#27=001
Open completion signal
(BFM#20480)
Internal
processing
Internal
processing
Power-on
Parameter
update completed
1)
2)
3)
4)
6)
7)
OPEN/CLOSE instruction
and status BFM#1602
R0005H
R
0000H
R
0000H
W0001H
W
8000H
R
0009H
1) After communicating the parameter settings, confirm the normal
completion of the Ethernet module initial processing.
(Initial normal completion signal (BFM#27"0001
H
"))
2) Start the open processing by writing 0001H to the BFM#1602.
(Open request signal (BFM#20482 b0)
: ON
3) The Ethernet module executes the open processing. (Internal
processing only)
4) When the open processing completes normally
• Open completion signal (BFM#20482 b0)
: ON
• Reading value of BFM#1602
: 0005
H
Data communication is enabled.
When the open processing completes abnormally
• Open status (BFM#1602)
: Value other than
0010
H
or 0015
H
• Open abnormal detection signal (BFM#28 b6)
: ON
5) Start the close processing by writing 8000
H
to the BFM#1602.
6) The Ethernet module executes the close processing. (Internal
processing only)
7) When the close processing completes normally
• Open/Close instruction status (BFM#1602)
: 0000
H